BOILER INSTALLATION, OPERATION
INSTRUCTIONS
Savio FP
WALL HUNG GAS BOILER FOR
CENTRAL HEATING SUPPLY
Please Read Instructions Carefully
Save for Future Reference
Do not store or use gasoline or other ammable vapors and liquids
in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your
building.
Immediately call your gas supplier from a neighbors phone. Fol-
low the gas suppliers instructions.
If you can not reach your gas supplier call the re department.
Installation and service must be performed by a quali ed installer,
service agency or the gas supplier.
WARNING: If the information in this manual is not followed
exactly, a re or explosion may result causing property dam-
age, personal injury or loss of life.
SAVIO FP MANUAL
Seitenansicht 0
1 2 3 4 5 6 ... 47 48

Inhaltsverzeichnis

Seite 1 - Savio FP

BOILER INSTALLATION, OPERATIONINSTRUCTIONSSavio FPWALL HUNG GAS BOILER FORCENTRAL HEATING SUPPLYPlease Read Instructions CarefullySave for Future Refe

Seite 2

10 SAVIO FP MANUALParts List3. Primary Components:1 Pump2 Pump vent plug3 Automatic air purger valve4 Modulation gas valve5 Flame-detecting electr

Seite 3 - Table of Contents

SAVIO FP MANUAL 11Internal Piping & Parts List4. 24 2613193111 10 2814 15 16 17 219 30 39 3637 1820232238 3233 34 35 25765429Note: Pressure Relie

Seite 4

12 SAVIO FP MANUALElectric Diagrams5. Air pressure switch ye bk wh gy bu rdbkgygygyM~tCOMNOM~COMNONC123bkbubnwhrdgnyegywhburdbkbuwhgybugnyebk bkbugey

Seite 5

SAVIO FP MANUAL 135. Electric Diagrams Cont.Sequence of Operation5.1 Is primary circuit temp higher than selected tempRequest for heat from thermost

Seite 6

14 SAVIO FP MANUALInstallation Location6. The installation location chosen must:Comply with all clearances listed below.• Provide suitable location f

Seite 7 - IMPORTANT INFORMATION

SAVIO FP MANUAL 15Exhaust Pipe Location7. CAUTIONEXTERNAL VENT SURFACES ARE HOT.IT IS RESPONSABILITY OF THE HOMEOWNER TO KEEP THE VENTTERMINAL CLEAR

Seite 8 - General Information1

16 SAVIO FP MANUALMounting Bracket8. After a suitable installation location is chosen, verify that the mounting wall is properly braced and strong en

Seite 9 - 2 16.5% 8.1%

SAVIO FP MANUAL 17Ventilation9. The SAVIO is a mechanical draft, side wall vented boiler. There are two side wall fl ue options available – separate a

Seite 10 - Parts List3

18 SAVIO FP MANUAL9. Ventilation Cont.The SAVIO is a mechanical draft, side wall vented boiler. There are two fl ue options available - separate and c

Seite 11 - SAVIO FP MANUAL 11

SAVIO FP MANUAL 199. Ventilation Cont.Choice of ue:9.3 The following fl ue kits are available for connecting to the boiler:A Standard coaxial horiz

Seite 12 - Electric Diagrams5

2 SAVIO FP MANUALDear Customer:Thank you for buying a SAVIO FP Boiler System.The SAVIO FP is a high effi ciency, non-condensing, wall mounted gas boil

Seite 13 - 5. Electric Diagrams Cont

20 SAVIO FP MANUAL9. Ventilation Cont.B Standard separate horizontal fl ue kit (Exhaust & intake outside)Figure 9.4 (Twin pipe φ 3.25 in)Various

Seite 14 - Installation Location6

SAVIO FP MANUAL 219. Ventilation Cont.C Alternative separate kit (Exhaust outside & intake inside)Figure 9.5 (Twin Pipe φ 3.25 in)This confi gura

Seite 15 - Exhaust Pipe Location7

22 SAVIO FP MANUAL9. Ventilation Cont.D Alternative separate kit (Exhaust outside & intake inside)Figure 9.6 (Twin Pipe φ 3.25 in)This confi gura

Seite 16 - Mounting Bracket8

SAVIO FP MANUAL 239. Ventilation Cont.E Alternative separate kit (Exhaust & intake outside)Figure 9.7 (Twin Pipe φ 3.25 in)These kits allow for

Seite 17 - Ventilation9

24 SAVIO FP MANUAL9. Ventilation Cont.F Standard Vertical-roof kit (Exhaust & intake outside)Figure 9.8 (vertical pipe φ 3.1 / φ 4.9 in)This kit

Seite 18 - 9. Ventilation Cont

SAVIO FP MANUAL 25Pipe Connections10. The SAVIO boiler is supplied with a 3/4” stainless steel gas pipe (A in fi gure 10.1), 2 - 3/4” cop-per pipe (C,

Seite 19

26 SAVIO FP MANUALGas Pipe Connections11. Gas supply piping is to be sized and installed properly in order to provide a supply of gas suffi -cient to

Seite 20

SAVIO FP MANUAL 27Electrical Connections/Wiring12. Figure 12.1 Removing Front Panel:Remove the front panel by removing screws A • and sliding the fr

Seite 21

28 SAVIO FP MANUAL12. Electrical Connections/Wiring Cont.Room Thermostat Connection:12.3 The room thermostat must be connected • to the terminal bloc

Seite 22

SAVIO FP MANUAL 2912. Electrical Connections/Wiring Cont.Zone Valve Micro Switch Connection:12.5 The zone valve micro switch must be con-• nected to

Seite 23

SAVIO FP MANUAL 3Table of ContentsSection Title Section Number Page NumberWarnings - 5-6Important Information - 7General Information 1 8Techni

Seite 24

30 SAVIO FP MANUALCirculator Sizing13. Circulator capacity as a function of ow rate:13.1 Figure 13.1 The hydraulic speci cation in Fig 13.1 repre

Seite 25 - Pipe Connections10

SAVIO FP MANUAL 31Piping14. All external piping components are to be supplied by the installer. It is very important to use a Primary Secondary pipin

Seite 26 - Gas Pipe Connections11

32 SAVIO FP MANUAL14. Piping Cont.Primary – Secondary Piping:14.1 All external piping components are to be supplied by the installer.It is very impor

Seite 27 - SAVIO FP MANUAL 27

SAVIO FP MANUAL 3314. Piping Cont.Primary – Secondary Piping with Zone Valves:14.2 All external piping components are to be supplied by the installer

Seite 28 - External controls

34 SAVIO FP MANUAL14. Piping Cont.Manifold Piping with Zone Valves or Circulators (shown conn. to radiators):14.3 All external piping components are

Seite 29 - To the external

SAVIO FP MANUAL 35Commissioning15. Initial lling of the system:15.1 Remove the front panel of the case.• Unscrew the cap on the automatic air • pur

Seite 30 - Circulator Sizing13

36 SAVIO FP MANUAL15. Commissioning Cont.Checking the gas pressure at the burner:15.3 This boiler has been tested to the highest quality control stan

Seite 31 - Piping14

SAVIO FP MANUAL 3715. Commissioning Cont.Adjustment of the gas pressure:15.4 Remove the front panel of the case.• Open the gas valve inlet pressure t

Seite 32 - 14. Piping Cont

38 SAVIO FP MANUAL15. Commissioning Cont.Checking the burner ignition:15.6 Turn the boiler OFF.• Open the gas valve outlet pressure test point • 15 (

Seite 33

SAVIO FP MANUAL 39Labels placement:15.8 Figure 15.10 Warning: The installation is not complete unless labels supplied are placed on the boil-er as

Seite 34

4 SAVIO FP MANUALTable of ContentsSection Title Section Number Page NumberPiping 14 31-34Primary – Secondary Piping 14.1 32Primary-Secondary with

Seite 35 - Commissioning15

40 SAVIO FP MANUAL15. Commissioning Cont.Checking the ue system and combustion:15.9 The fl ue system should be visually checked for soundness. Check

Seite 36 - 15. Commissioning Cont

SAVIO FP MANUAL 41Gas Conversion16. WARNINGS: Procedures to adapt the boiler to the type of gas available must be car-ried out by a competent and re

Seite 37

42 SAVIO FP MANUALAnnual Maintenance17. Warnings:17.1 The procedures detailed in this chapter must be carried out only by a professionally qualifi ed

Seite 38

SAVIO FP MANUAL 4317. Annual Maintenance Cont.Cleaning the primary heat exchanger:17.5 Take off the front panel of the case, then the sealed chamber

Seite 39

44 SAVIO FP MANUALVent Part Spares18. Description Order NumberTwin pipe kit 10999.0393.0For any spare parts, please contact BOYERTOWN 1-610-369-1450.

Seite 40

SAVIO FP MANUAL 4518. Vent Part Spares Cont.Description Order NumberCoaxial fl ue kit 10999.0387.0For any spare parts, please contact BOYERTOWN 1-610-

Seite 41 - Gas Conversion16

46 SAVIO FP MANUAL18. Vent Part Spares Cont.Part Description Order NumberA Roof fl ue kit 10999.0392.0For any spare parts, please contact BOYERTOWN 1-

Seite 42

SAVIO FP MANUAL 47Installer Notes19. System Checkout:Boiler Model No. ___________________Original Purchaser:_________________________________________

Seite 43 - Venturi test

17962.1511.0 3808 (52A4)USA19/092008N

Seite 44 - Vent Part Spares18

SAVIO FP MANUAL 5WARNINGDANGERBoiler is certifi ed as an indoor appliance. Do not install boiler outdoors or locate where it will be exposed to freezi

Seite 45 - 18. Vent Part Spares Cont

6 SAVIO FP MANUALWARNINGAny appliance that burns natural gas, propane gas, fuel oil, wood or coal is capable of pro-ducing carbon monoxide (CO). Carb

Seite 46

SAVIO FP MANUAL 7IMPORTANT INFORMATIONPlease read this page carefully.ALL BOILERS MUST BE INSTALLED IN ACCORDANCE WITH NATIONAL, • STATE AND LOCAL PL

Seite 47 - Installer Notes19

8 SAVIO FP MANUALGeneral Information1. Technical Information (M130.30CM)2. The SAVIO FP is a high effi ciency, non-condensing, wall mounted gas boiler

Seite 48 - 17962.1511.0 3808 (52A4)USA

SAVIO FP MANUAL 92. Technical Information Cont.ENERGY CAPACITYNominal heat input (0/2000ft)MBH 122.8Nominal heat input (2000/4500ft)MBH 116.7Minimum